Country of Origin: GERMANY
Model: FLM-420
- Semi-conductor output electrically isolated from LSN
Loop and short-circuit proof
- Max. switchable current per output 700 mA
- Individually selectable input monitoring functions
(EOL or contact)
- Maintains LSN loop functions in the event of wire
interruption or short-circuit thanks to two integrated
isolators
Functions
Semi-conductor output
The semi-conductor output is electrically isolated from the
LSN loop and protected against short circuits.
Output power supply
The power supply for loads connected to the output can
be selected as:
• Auxiliary power supply from the fire panel
• External power supply units.
Input monitoring functions
The FLM‑420‑O1I1 Output-input-Interface Module
provides two monitoring functions:
1. Monitoring of a line by an EOL resistor
2. Monitoring of a potential‑free contact
The input monitoring functions can be selected by setting
the corresponding addresses.
Line monitoring with EOL resistor
The EOL resistor has a standard resistance of 3.9 kΩ.
The interface module detects
• Standby
• Triggering in the event of a short circuit
• Triggering in the event of line interruption.
Position Description
RΣ Overall line resistance with RΣ = RL/2 + RL/2 + REOL
RL/2 Line resistance
The following line conditions will be reliably detected if
the overall line resistance is within the specified range:
Line condition Overall line resistance RΣ
Standby 1500 Ω to 6000 Ω
Short circuit < 800 Ω
Interruption > 12.000 Ω
Contact monitoring
The interface module evaluates the operating conditions
“open” or “closed”. The normal operating condition can be
programmed for each input. Contact monitoring has a
pulse intensity of 8 mA.
LSN features
Integrated isolators ensure that function is maintained in
the event of a short circuit or line interruption in the LSN
loop. A fault indication is sent to the fire panel.
Features of LSN improved version
The interface modules in the 420 series offer all the
features of improved LSN technology:
• Flexible network structures including T‑tapping
without additional elements
• Up to 254 LSN improved elements per loop or stub
line • Unshielded cable can be used
Interface variants
The Output-input Interface Modules are available in
various designs:
• FLM‑420‑O1I1‑E in-built version:
– Suitable for standard device boxes according to
EN 60670 and
– For a space-saving installation in all devices.
• FLM‑420‑O1I1‑D DIN-rail version:
– Suitable for installation on a DIN-rail according to
EN 60715 with included adapter and
– For the FLM‑IFB126‑S surface-mounted housing.
Technical Specifications
Electrical
LSN
• LSN input voltage 15 V DC to 33 V DC
• Max. current consumption
from LSN
1.9 mA
Output
• Max. switchable voltage of
semi-conductor output
30 V DC
• Max. switchable output
current
700 mA (depending on external power
supply)
• External power supply 5 V DC to 30 V DC
Input
Line monitoring with EOL
• EOL resistor Nominal 3.9 kΩ
• Overall line resistance RΣ
with RΣ = RL/1 + RL/
2 + REOL
• Standby: 1500 Ω to 6000 Ω
• Short circuit: < 800 Ω
• Line interruption: > 12.000 Ω
Contact monitoring
• Max. current strength
(current pulse)
8 mA
Minimum activation time of the
input
3.2 s
Mechanical
Connections
• FLM-420-O1I1-E 14 screw terminals
• FLM-420-O1I1-D 12 screw terminals
Permissible wire diameter
• FLM-420- O1I1-E 0.6 mm2 to 2.0 mm2
• FLM-420- O1I-D 0.6 mm2 to 3.3 mm2
Address setting
• FLM-420- O1I1-E 8 DIP switches
• FLM-420- O1I1-D 3 rotary switches
Housing material
• FLM-420- O1I1-E ABS/PC blend
• FLM-420- O1I1-D incl.
adapter
PPO (Noryl)
Housing color
• FLM-420- O1I1-E Signal white, RAL 9003
• FLM-420- O1I1-D incl.
adapter
Gray white, similar to RAL 9002
Dimensions
• FLM-420- O1I1-E Approx. 50 mm x 22 mm (Ø x H)
• FLM-420- O1I1-D incl.
adapter
Approx. 110 x 110 x 48 mm
(W x H x D)
Weight Without/with packing
• FLM-420- O1I1-E Approx. 35 g / 170 g
• FLM-420-O2-D Approx. 95 g / 390 g
Environmental conditions
Permissible operating temperature
-20 °C to +65 °C
Permissible storage temperature -25 °C to +80 °C
Permissible rel. humidity < 96% (non-condensing)
Classes of equipment as per
IEC 60950
Class III equipment
Protection class as per
IEC 60529
IP 30
System limiting values
Maximum cable length input 3 m
Maximum cable length output 3 m
Related products
-
BOSCH FPA-5000 Modular Fire Panel
Read moreThe Fire Panel is Available with Two Different Housings:
- Housing for mounting directly on the wall
- Frame installation housings which are fitted to the mounting frame and can be swiveled.
With the aid of special mounting kits, the housings can be mounted in 482.6 mm (19″) cabinets. All housings can be extended with various additional housings for all conceivable applications.
-
Best offers
Join Risk Free
30 days refund
100% Safe
Secure Shopping
24x7 Support
Online 24 hours
Best Offers
Shop Now
Shipping Cost
Very Low Cost












Reviews
There are no reviews yet.